77. How to Establish Communication Between i Series HMI and S7-1200 FW V4.0 devices?
Recently, Siemens has made great changes in S7-1200 Firmware V4.0; therefore, S7-1200 driver can no longer establish communication between EasyBuilder8000 and S7-1200 Firmware V4.0. To establish communication between i Series HMI and S7-1200 Firmware V4.0 devices, please use S7-1500 driver.
Please follow the steps to set up the environment for communication, otherwise, error may occur.
Step 1. Select [General] » [Protection] » [Permit access with PUT/GET communication from remote partner] option.
Step 2. Please do not select [DB UTILITAIRES] » [Attributes] » [Optimized block access]. Note that the option in all Data Blocks should not be selected.
The following part explains how to import address tags using TIA.
Step 1. Export PLC Tags (.xlsx file format). Under [PLC tags] create the address tags and then click the Export icon.
Designate the directory to save the file and then click OK button.
Step 2. Export Data Blocks (.scl file format). Under [Data blocks] create “Data_block_1 [DB1]” as shown in the following figure. Click the right mouse button on [DB1] and then click [Generate source from blocks] to generate .scl file.
Step 3. In EasyBuilder8000, click [New PLC…], select “Siemens S7-1500 (Ethernet)”, and then click [Settings…] to set the parameters.
Step 4. Click [Import Tag…] button.
Step 5. Select the PLC tags and Data Blocks to be imported. Pease check if the DB Number is correct.
Step 6. Click [Import], a message will be displayed after successful import, click OK button to leave.
Supported data types:
Byte 16-bit BCD, Hex, Binary, Unsigned 8-bit SInt 16-bit BCD, Hex, Binary, Signed 8-bit USInt 16-bit BCD, Hex, Binary, Unsigned 8-bit Word 16-bit BCD, Hex, Binary, Unsigned 16-bit Int 16-bit BCD, Hex, Binary, Signed 16-bit UInt 16-bit BCD, Hex, Binary, Unsigned 16-bit DWord 32-bit BCD, Hex, Binary, Unsigned 32-bit
DInt 32-bit BCD, Hex, Binary, Signed 32-bit
Real 32-bit Float 32-bit
UDInt 32-bit BCD, Hex, Binary, Unsigned 32-bit
Array Word array for ASCII input and display Length=word