11. Ethernet Pass-Through Communication
MT8000 provides Ethernet pass-through communication which allows PC to link to the PLC through the HMI. In this situation, the role of HMI is similar to a converter.
First, a virtual serial port must be created on PC. The application program on PC can communicate with PLC through this virtual serial port.
Instructions are as follows:
1. Open Project Manager and click the [ Pass-through] button ;
2. Check the [Ethernet] radio box, and click [ Install] button to install the virtual serial port driver ;
3. Installing driver ...
4. Click [ Continue Anyway]
5. Virtural seriel port installation completed. A new virtual COM port number is found ;
6. Check out the [ Computer Management] to see if the virtual COM port is
successfully installed.
7. Select the [ Virtual Serial Port] and click right key . Select [Properties ] to change COM port number ;
8. Take communication between Fatek PLC and MT8000 for example, if the MT8000 HMI IP address is 192.168.1.200, the PLC parameter settings are as follows :
9. In the [ Pass-through] window, setup the HMI IP address : 192.168.1.200 ; Set the COM port number to COM1, which is the communication port number between MT8000 and the PLC ; The COM port type is RS232, which is the communication port type between MT8000 and the PLC ; These settings are according to the window shown above ; Click [ Apply] button.
10. Open the Fatek PLC software : WinProladder ; Select [On-Line] under PLC menu ;
11. Set the COM port ;
12. Set the COM port number to COM3, which is the Virtual Serial Port number that you get in step 5 ;
13. Connection succeeded ;
14. PC-HMI-PLC connection example ;