Komunikacja HMI serii i z Siemens S7-1200 FW V4.0

Streszczenie: Komunikacja paneli serii i z Siemens S7-1200 z firmware V4.0: należy użyć sterownika S7-1500, włączyć w PLC dostęp PUT/GET i wyłączyć „Optimized block access” w blokach danych; import tagów z TIA Portal (.xlsx i .scl).
EN: How to communicate i series HMIs with Siemens S7-1200 FW V4.0 using the S7-1500 driver, PUT/GET access and non-optimized data blocks; importing tags from TIA Portal.

Dotyczy: panele HMI Weintek serii i, Siemens S7-1200 FW V4.0, TIA Portal
Źródło: Weintek FAQ (materiały producenta), oryginalny tytuł: „How to Establish Communication Between i Series HMI and S7-1200 FW V4.0 devices?”

Recently, Siemens has made great changes in S7-1200 Firmware V4.0; therefore, S7-1200 driver can no longer establish communication between EasyBuilder8000 and S7-1200 Firmware V4.0. To establish communication between i Series HMI and S7-1200 Firmware V4.0 devices, please use S7-1500 driver.

Please follow the steps to set up the environment for communication, otherwise, error may occur.
Step 1. Select [General] » [Protection] » [Permit access with PUT/GET communication from remote partner] option.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Select [General] » [Protection] » [Permit access with PUT/GET communication from remote partner] option.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Step 2. Please do not select [DB UTILITAIRES] » [Attributes] » [Optimized block access]. Note that the option in all Data Blocks should…

Step 2. Please do not select [DB UTILITAIRES] » [Attributes] » [Optimized block access]. Note that the option in all Data Blocks should not be selected.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Note that the option in all Data Blocks should not be selected.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0

The following part explains how to import address tags using TIA.
Step 1. Export PLC Tags (.xlsx file format). Under [PLC tags] create the address tags and then click the Export icon.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Under [PLC tags] create the address tags and then click the Export icon.

Designate the directory to save the file and then click OK button.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Designate the directory to save the file and then click OK button.

Step 2. Export Data Blocks (.scl file format). Under [Data blocks] create “Data_block_1 [DB1]” as shown in the following figure. Click the right mouse button on [DB1] and then click [Generate source from blocks] to generate .scl file.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Click the right mouse button on [DB1] and then click [Generate source from blocks] to generate .scl file.

Step 3. In EasyBuilder8000, click [New PLC…], select “Siemens S7-1500 (Ethernet)”, and then click [Settings…] to set the parameters.
Step 4. Click [Import Tag…] button.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Click [Import Tag…] button.

Step 5. Select the PLC tags and Data Blocks to be imported. Pease check if the DB Number is correct.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Pease check if the DB Number is correct.

Step 6. Click [Import], a message will be displayed after successful import, click OK button to leave.

image.pngIlustracja: Komunikacja HMI serii i z Siemens S7-1200 FW V4.0 – Click [Import], a message will be displayed after successful import, click OK button to leave.

Supported data types:

S7-1200 Data Type EasyBuilder Data Format Memo
Bool bit
Byte 16-bit BCD, Hex, Binary, Unsigned 8-bit
SInt 16-bit BCD, Hex, Binary, Signed  8-bit
USInt 16-bit BCD, Hex, Binary, Unsigned 8-bit
Word 16-bit BCD, Hex, Binary, Unsigned 16-bit
Int 16-bit BCD, Hex, Binary, Signed  16-bit
UInt 16-bit BCD, Hex, Binary, Unsigned 16-bit
DWord 32-bit BCD, Hex, Binary, Unsigned 32-bit
DInt 32-bit BCD, Hex, Binary, Signed 32-bit
Real 32-bit Float 32-bit
UDInt 32-bit BCD, Hex, Binary, Unsigned 32-bit
Array Word array for ASCII input and display Length=word

 

 

Słowa kluczowe

Siemens, S7-1200, firmware V4.0, S7-1500 driver, PUT/GET, Optimized block access, TIA Portal, import tagów, Data Block, DB1, .scl, .xlsx, Ethernet, How to Establish Communication Between i Series HMI and S7-1200 FW V4.0 devices?