4. Wiring & Connection
4.1 Precautions for Cable Connection
The cable connection between control cabinet and peripheral equipment should be carried out without power in the control cabinet.
The signal cables of the control cabinet shall be laid in a distance far away from the main power supply circuit, while the HV power supply line shall not be parallel to the signal cables of the control cabinet. Where unavoidable, metal tube or metal slot shall be used to prevent the interference of electric signal. If the cables must be arranged in a cross way, the power cables and signal cables shall be laid in a perpendicular way
Confirm the socket and cable number to prevent equipment damage arising from incorrect connection.
All non-workers shall be evacuated from the site when connecting cables. Be sure to put all cables in underground cable trench with cover.
Connect the control cabinet's ground wire to the earth for improved EMC performance.
The wiring and routing of encoder cables must be separated from power cables. If they are placed in the same cable conduit, isolators must be used to keep them separated.
4.2 Basic Connection Diagram
The fundamental connection diagram for the control cabinet includes the robot body, control cabinet, teach pendant, surge protector, and circuit breaker.
Figure 4-2 Basic Connection Diagram
4.3 Circuit Breaker/Surge Protector Selection
4.3.1 Circuit breaker
The robot's motion trajectory involves a repetitive acceleration-deceleration process. As a result, the control cabinet experiences repetitive instances of high transient current in its input. This imposes specific requirements on the rated current and type of upstream circuit breakers or disconnectors. Additionally, being a frequencycontrolled industrial device, the design and operational principles of the robot control cabinet inherently lead to a certain level of leakage current.
The circuit breaker specifications should meet the requirements in the table below.
a) It is recommended to provide each robot control cabinet with a circuit breaker/air switch that meets the robot's load current, with a momentary impulse current of 200A during power-up and the ability to cut off a short-circuit current of 5KA. The leakage protection should use a Type B residual current circuit breaker with a sensitivity current ≥300mA.
b) If connecting multiple devices under one circuit breaker or air switch with a leakage protector, the current value and leakage current protection value of the air switch or circuit breaker should be multiplied based on the configuration value of a single unit.
4.3.2 Surge protector
It is advisable to add a suitable surge protector (SPD) at the power input of the control cabinet to meet the requirements of UL1740.
4.4 Power Cable Selection
ESTUN control cabinets are not equipped with input power cables. Users need to provide their wiring or purchase from ESTUN. When choosing cables, comply with the relevant safety standards. The recommended cable specifications are as follows.
4.5 Power Supply Wiring
Description
The control cabinet uses a three-phase AC 380V power supply. Follow the provided diagram for proper power cable assembly and correct wiring. Pay attention to the following connections:
Power Harness Assembly
When wiring the power supply cable, please note that it should be routed in the following way as shown in Figure 4-3:
Connect the L1, L2, L3 three-phase power lines from the power grid to the upper space of the load switch inside the control cabinet. Connect the PE line to the grounding bar inside the control cabinet, as shown in Figure 4-4.
4.6 Teach Pendant
4.6.1 Precautions for using teach pendant
1. Handle with care and avoid dropping, throwing, or striking the teach pendant, as this may cause damage or malfunction. When not in use, hang it on the dedicated holder to prevent accidental dropping (our internal drop test result is satisfactory at a height of 1 M);
2. Do not use sharp objects such as screws, knives, or pen tips to operate the touch screen. This may damage the touch screen. Use your fingers or a stylus pen to operate the touch screen;
3. When no USB devices are connected, make sure to cover the USB ports with protective caps to avoid exposing them to dust, which could cause interruptions or failures;
4. When using USB plugs, do not apply excessive force. Normal use is sufficient;
5. If the USB is not recognized, unplug the USB drive, power off, and then plug it back in after powering on;
6. When using the E-stop button or key, do not apply excessive force. Normal use is sufficient;
7. The power-on time is 40 seconds for the system to start up properly. Do not power off prematurely to avoid file loss;
8. When storing cables, do not place them under heavy machinery to avoid crushing, cutting, or pulling them apart;
9. Follow our defined wiring guidelines to avoid connection errors and potential issues;
10. The teach pendant is not explosion-proof. Do not use it in explosive environments or work units;
11. Keep the teach pendant away from water, oil, and similar environments;
12. The new T76 teach pendant can be used with all models, while the T72 is only compatible with PNP module control cabinets.
4.6.2 Appearance of teach pendant
4.6.3 Teach pendant interface definition
4.6.4 Specificatios of teach pendant
4.7 IOWiring
This chapter primarily introduces the DI/DO interfaces of functional safety control cabinets configured as a standard. The functional safety series control cabinets are provided with two IO modules: DM1 and DM2. Each IO module is configured with 16 channels of DI and 16 channels of DO. In the case of the DM1 module, the DI section has 10 channels (DI0~DI9) occupied by the system, and the DO section has 1 channel dedicated to system 8DO (DO0~DO7). Users have the flexibility to customize the usage of 6 channels of DI (DIA~DIF) and 8 channels of DO (DO8~DOF). All the IO on the DM2 module is available for user customization.
The IO modules of the functional safety control cabinets are positioned within the cabinet as illustrated in Figure 4 below.
Figure 4-7 IO Module Position
4.7.1 IO Signal specifications
The technical specificationsof the digital I/O expansion module EC4-1616BWE are shown in Table 4-3 below.
4.7.2 System DI
The DI0~DI9 of the DM1 module within the control cabinet have been designated as system DI, their definitions and functions have been predetermined and cannot be altered. The specific definitions and functions are outlined in the table below.
[Note] * indicates that these ports are occupied by the control cabinet and cannot be used by users.
The specific wiring methods for system DI are as follows:
[Note]: When powered by internal 24V, the total load current of all DI and DO modules must not exceed 1A.
[Note]: When powered by an external 24V source, it's necessary to disconnect the wiring between the 24V on the IO module and the internal 24V (19), as well as between the 0V on the IO module and the internal 0V (20), and ensure proper insulation.
4.7.3 System DO
The DO0~DO7 ports on the DM1 module have been designated as system DO, with specific definitions outlined in the table below:
[Note]: * indicates that these ports are occupied by the control cabinet and cannot be used by users.
The specific wiring methods for system DO are illustrated as follows:
[Note]: When powered by internal 24V source, the total load current of all DI and DO modules must not exceed 1A.
[Note]: When powered by an external 24V source, it's necessary to disconnect the wiring between the 24V on the IO module and the internal 24V (19), as well as between the 0V on the IO module and the internal 0V (20), and ensure proper insulation.
4.7.2 General DI
DM1 module reserves 10 channels of DI (DI0~DI9) for system use, allowing users to use 6 channels of DI (DIA~DIF). All DI on the DM2 module is available for user customization.
The specific wiring methods for general DI are depicted as follows:
[Note]: When powered by internal 24V source, the total load current of all DI and DO modules must not exceed 1A.
[Note]: When powered by an external 24V source, it's necessary to disconnect the wiring between the 24V on the IO module and the internal 24V (19), as well as between the 0V on the IO module and the internal 0V (20), and ensure proper insulation.
4.7.3 General DO
DM1 module reserves 8 channels of DO (DO0~DO7) for system use, allowing users to customize 8 channels of DO (DO8~DOF). All DO on the DM2 module is available for user customization.
The specific wiring methods for general DO are illustrated as follows:
[Note]: When powered by internal 24V source, the total load current of all DI and DO modules must not exceed 1A. The load R can be relay coils, indicator lights, or input terminals of customer DI modules.
[Note]: When powered by an external 24V source, it's necessary to disconnect the wiring between the 24V on the IO module and the internal 24V (19), as well as between the 0V on the IO module and the internal 0V (20), ensuring proper insulation. The load R can be relay coils, indicator lights, or input terminals of customer DI modules.
4.7.4 Reserved DI/DO cables
The functional safety control cabinet has reserved a specific number of IO cables to connect to the robot's IO cable interface, intended for tooling or fixture equipment on the robot. These reserved IO cables within the cabinet are not electrically connected. Users can connect the reserved IO cables to the IO module based on actual functional requirements. The specific breakout locations for reserved IO cables are depicted in Figure 4-18 below, with pin definitions outlined in Table 4-7.
4.8 SAFETY IO
The functional safety robot control cabinets offer diverse safety stop methods, and the specific SAFETY IO interface is illustrated in the figure below.
By default, shorting jumpers are inserted into the SAFETY IO, rendering the corresponding functions inactive. To use these functions, the respective shorting jumpers must be removed, and connections must be installed following the appropriate wiring methods.
It is strongly advised not to remove the shorting jumpers if these functions are not in use, as doing so may trigger the corresponding functionalities, leading to operational halts or alarms
The input/output signals and functionalities related to safety stop are detailed in Table 4.8 below:
4.8.1 SAFETY IO interface specification
[Note]: SAFETY IO is prohibited for driving external loads!
4.8.2 External E-stop wiring method
The External E-Stop function allows users to trigger an emergency stop away from the control cabinet, similar to the functionality of the E-Stop button on the cabinet. Users can incorporate a self-provided E-stop button into the circuit.
The specific wiring method is depicted in Figure 4.20:
If you use a dual-channel external emergency stop, you need to remove the external shorting tabs, connect the upper end of one circuit of the pushbuttons to ES1+ and the lower end to ES1-; the upper end of the other circuit is connected to ES2+ and the lower end is connected to ES2-, so that it becomes a circuit to be energised and can be operated.
4.8.3 Auto Stop wiring method
The Auto Stop function allows stopping the robot's motion during operation, used as safety doors or light curtains.
It's employed to secure protective barriers or doors during robot operation. The wiring method is shown in the diagram below.
4.8.4 Halt Stop wiring method
The Halt Stop function is only applicable in automatic mode outside the safety fence. It enables users near the safety fence or light curtain to initiate a slow stop. When activated, the robot stops for a duration before resuming operation. The specific wiring method is illustrated in Figure 4.24:
4.8.5 Start Confirmation/Reset wiring method
When using the Start Confirmation/Reset function, the SC signal is externally connected to a self-resetting normally open switch. Pressing the Start Confirmation/Reset button allows the control cabinet to provide power to the motors. The specific wiring method is depicted in the following diagram.
4.8.6 External E-Stop Output wiring method
The External E-Stop Output refers to the output signal of the External E-Stop function on SAFETY IO. The wiring methods are depicted in the figures below:
(1) Wiring method for a relay load
(2) Wiring method for a customer DI module load:
Note: The load current of all DI and DO modules must not exceed 1A when powered by the internal 24V
4.8.7 Cabinet E-Stop Output wiring method
The Cabinet E-Stop Output refers to the output signal when the E-Stop button on the control cabinet panel or the teach pendant is activated. The wiring methods are shown in the figures below:
(1) Wiring method for a relay load
(2) Wiring method for a customer DI module load
【Note】: The load current of all DI and DO modules must not exceed 1A when powered by the internal 24V power supply.
4.8.8 Auto Stop Output wiring method
The Auto Stop Output refers to the output signal of the Auto Stop function on SAFETY IO. The wiring methods are demonstrated in the figures below.
(1) Wiring method for a relay load
(2) Wiring method for a customer DI module load
Note: The load current of all DI and DO modules must not exceed 1A when powered by the internal 24V power supply.
4.8.9 Halt Stop Output wiring method
The Halt Stop Output refers to the output signal of the Halt Stop function on SAFETY IO. The wiring methods are delineated in the diagrams below:
(1) Wiring method for a relay load
(2) Wiring method for a customer DI module load
Note: The load current of all DI and DO modules must not exceed 1A when powered by the internal 24V power supply.
4.9 Powerline Interconnect Cable Wiring
Connect the male connector on the robot power line interconnection cable to the robot power line interface on the control cabinet, and then connect the female connector to the corresponding power line interface on the robot body, then complete the wiring of the power line interconnection cable
4.10 Encoder Interconnection Cable Wiring
Connect the female connector on the robot encoder interconnect cable to the encoder cable connector on the control cabinet, and then connect the male connector to the corresponding encoder cable connector on the robot body to complete the wiring of the encoder interconnect cable.
4.11 Controller
The controller is the motion control device of the robot system, which receives instructions from the teach pendant and sends control signals. It is the core component of the system.
































































No comments to display
No comments to display